User Tools

Site Tools


troubleshooting

Troubleshooting

MIG Software Error

  • Error Code: -229771
  • Message: Internal Software Error occurred in MIG software. Please contact National Instruments Support.
  • Cause: NI MAX configuration database is broken. Input and output channels disappeared.
  • Solution: NI MAX database reset and installation of backup configuration.
  • Step-by-Step:
    1. Open NI MAX (Measurement & Automation Explorer)
    2. Select Tools → Reset Configuration Data
    3. Restart PC
    4. Select File → Import to install backup configuration
  • Prevention:
    • Avoid conflicts of NI drivers with other programs such as virus scanners or backup processes
    • MAX Database corruptions may be caused when a system reboots without being properly shut down due to a power loss or a system crash
    • Always keep an up-to-date backup of the MAX configuration by selecting File → Export
troubleshooting.txt · Last modified: 2017/09/20 14:39 by dennis